Page 79 - index
P. 79



NET WT
®
Firewall LSZH RW90 PART NUMBER COND. SIZE (AWG) NO. OF STRANDS INS THICKNESS NOM. OVERALL DIAM LBS/1000 FT
INCHES
INCHES
FRRW-014-001 14 AWG 7 0.045 0.16 24
Low Smoke • Zero Halogen • 90ºC* • 1000 VoltCEC FRRW-012-001 12 AWG 7 0.045 0.18 34
FRRW-010-001 10 AWG 7 0.045 0.21 48
Type RW90 CUL Listed • NFPA 130 & 502 FRRW-008-001 8 AWG 7 0.045 0.24 70

FRRW-006-001 6 AWG 7 0.060 0.3 114
FEATURES FRRW-004-001 4 AWG 7 0.060 0.35 170
FRRW-003-001 3 AWG 7 0.060 0.38 206
• Low Smoke Zero Halogen Design
• RoHS compliant insulation FRRW-002-001 2 AWG 7 0.060 0.41 251
• Thermoset insulation for enhanced thermal stability FRRW-001-001 1 AWG 19 0.080 0.49 332
• Specially formulated insulation for exceptional long term water resistance FRRW-110-001 1/0 AWG 19 0.080 0.53 406
• Superior fame retardance FRRW-210-001 2/0 AWG 19 0.080 0.57 501
• Excellent mechanical properties FRRW-310-001 3/0 AWG 19 0.080 0.62 619
• Tin-coated copper conductors for improved terminations and corrosion resistance FRRW-410-001 4/0 AWG 19 0.080 0.68 765
• Reduced size and weight for increased raceway capacity FRRW-250-001 250 kcmil 37 0.090 0.75 900
• Easy strippability FRRW-350-001 350 kcmil 37 0.090 0.85 1225
• Low friction surface for reduced pulling tension
FRRW-500-001 500 kcmil 37 0.090 0.98 1725
FRRW-600-001 600 kcmil 61 0.090 1.07 2040
PERFORMANCE STANDARDS
FRRW-750-001 750 kcmil 61 0.090 1.16 2575
• Insulation in accordance with ICEA and CEC standards
• CUL listed type RW90 (CSA 22.2 No.38) in accordance with CEC
• Passes IEEE 1202/FT4 vertical tray fame test ICEA 70,000 BTU/hr vertical fame test
• Passes vertical fame test Type A as defned in ICEA S-95-658 (6.8.2)
• CUL listed as Type ST1 (Limited Smoke) per UL 2556
• CUL approved 90º for both wet and dry locations
• CUL listed as gasoline and oil resistant
• Meets the requirements of NFPA 130 & 502
• Passes UL VW-1**
SCOPE
®
CONSTRUCTION Firewall LSZH RW90 is a one conductor, unjacketed, power
cable. Its tough thermoset construction allows for its use
• Conductor: Annealed, tin-coated copper, Class "B" strand per ASTM B-8 & B-33
in demanding applications without additional jacketing
(Available as solid conductors when required)
protection. It is intended for low voltage power and lighting
• Insulation: Flame retardant low Smoke Zero Halogen crosslinked polyolefn
functions and may be installed in trays, ducts and conduits.
• Separator Tape: Helically applied polyester (where required)
• Color: Black (Available in pigmented colors or colored stripes)


* Rated 90ºC for normal operation in wet and dry locations, 130ºC for emergency overload conditions, and 250ºC for short circuit conditions.
** #10 AWG and larger.















industrialsales@cobrawire.com | 216-416-0477 | www.cobrawire.com
© 2015 Cobra Wire & Cable, A Genuine Cable Group Company
A GENUINE CABLE GROUP COMPANY A DIVISION OF EIS, INC. 79
   74   75   76   77   78   79   80   81   82   83   84