VITALink MC Transit


90ºC* • 600 Volt • NEC Type MC UL Listed
UL Electrical Circuit Integrity System (FHIT 120)




FEATURES
• 2-hour fre rating
• Available as a VFD cable with segmented grounds
• Low smoke, halogen free design
• Simple to terminate with commercially available brass or stainless steel MC connectors
• Printed number coding allows for easy circuit identifcation
• Uses conventional tools for terminating
• Available in long lengths
• Welded armor forms an impervious barrier SCOPE
• Armor is impact & crush resistant VITALink MC Transit is a 600 volt power cable with a
®
• Fire-rated splice available (FHIT 120) 2-hour fre-rating when installed in accordance with the
VITALink Installation Manual and Installation Guide. This
APPLICATIONS cable meets the requirements of UL 2196 Fire Resistive
Cable Standard as a 2-hour "Electrical Circuit Integrity
Emergency circuits: System". It was specifcally designed to meet both the
• Ventilation electrical and fre-resistive cable requirements of NFPA
• Lighting 130 and NFPA 502 for Emergency Communications,
• Communications Emergency Lighting & Emergency Ventilation.


PERFORMANCE STANDARDS
• UL listed, NEC Type MC in accordance with UL Standard 1569
• UL listed as 2-hour fre rated in accordance with ANSI/UL 2196,
maximum 480 volts under fre conditions
• Electrical Circuit Integrity Systems (FHIT) - System No. 120 of the UL Fire Resistance Directory
• Meets and exceeds fre rated cable requirements in NFPA 130 for Transit applications
and NFPA 502 for Highway Tunnel applications
• Rated FT-4 / IEEE 1202 Vertical Flame test; ST1, limited smoke
• For use in wet locations to 90ºC
• Armored with copper sheath that exceeds the NEC requirement for equipment grounding conductor
• Complies with NFPA 130 and NFPA 502 for total smoke released and low toxicity


CONSTRUCTION
Conductor: Annealed copper, Class "B" strand per ASTM B-170 & B-8
Insulation: Thermoset, low smoke zero halogen silicone rubber
Circuit Identifcation: Printed numbers per ICEA Method 4
Inner Jacket: Thermoset, low smoke zero halogen silicone rubber
Armor: Continuously welded and corrugated copper
Outer Jacket: Black low smoke, zero halogen polyolefn (colors available on request)

* Rated 90ºC for normal operation, 130ºC for emergency overload conditions, and 250ºC for short circuit conditions.