Page 22 - index
P. 22



EPR/CPE 2.4kV MV-90



Medium-Voltage Power Cable
Nonshielded • 2400 Volts • UL Type MV-90




CONDUCTOR
• 8 AWG thru 1000 kcmil annealed bare copper compact Class B strand


EXTRUDED STRAND SHIELD (ESS)
• Extruded thermoset semi-conducting stress-control
layer over conductor

INSULATION

• Ethylene Propylene Rubber (EPR) insulation, colored
to contrast with the black jacket material


JACKET
• Lead-free Cross-linked Chlorinated Polyethylene (XL-CPE)


STANDARDS
Industry Compliances:
• National Electric Code (NEC)
• ICEA S-96-659/NEMA WC71
• UL 1072
• UL listed as Type MV-90 for use in accordance
with NEC, UL File # E90501
• Sizes 1/0 AWG and larger are listed and marked “FOR CT USE”
in accordance with NEC and also meet IEEE 383 (70,000 BTU/hr)
• Listed “oil-resistant I”
• Meets EPA 40 CFR, Part 261 for leachable
lead content per TCLP method
• OSHA acceptable




The frst successful trans-
Atlantic telegraph cable
was installed in 1858. It was
insulated with gutta-percha.
The 98 word message of
congratulations from Queen
Victoria of Great Britain to
President Buchanan took 16 1/2
hours to transmit.







industrialsales@cobrawire.com | 216-416-0477 | www.cobrawire.com
© 2015 Cobra Wire & Cable, A Genuine Cable Group Company
A GENUINE CABLE GROUP COMPANY A DIVISION OF EIS, INC.
22
   17   18   19   20   21   22   23   24   25   26   27