EPR/CPE 2.4kV MV-90
Medium-Voltage Power Cable
Nonshielded • 2400 Volts • UL Type MV-90
CONDUCTOR
• 8 AWG thru 1000 kcmil annealed bare copper compact Class B strand
EXTRUDED STRAND SHIELD (ESS)
• Extruded thermoset semi-conducting stress-control
layer over conductor
INSULATION
• Ethylene Propylene Rubber (EPR) insulation, colored
to contrast with the black jacket material
JACKET
• Lead-free Cross-linked Chlorinated Polyethylene (XL-CPE)
STANDARDS
Industry Compliances:
• National Electric Code (NEC)
• ICEA S-96-659/NEMA WC71
• UL 1072
• UL listed as Type MV-90 for use in accordance
with NEC, UL File # E90501
• Sizes 1/0 AWG and larger are listed and marked “FOR CT USE”
in accordance with NEC and also meet IEEE 383 (70,000 BTU/hr)
• Listed “oil-resistant I”
• Meets EPA 40 CFR, Part 261 for leachable
lead content per TCLP method
• OSHA acceptable