Page 46 - index
P. 46
FR-EPR/CPE Power 600V
Low-Voltage Power Cable • Unshielded • 600 Volts
UL Type TC-ER • Method 4 Color Code
1
CONDUCTOR
• 14 AWG thru 750 kcmil tinned, annealed copper per ASTM B33
• Class B stranding per ASTM B8
INSULATION
• Flame-Retardant Ethylene Propylene Rubber (FR-EPR) Type II
• Color-coded per ICEA Method 4; individual conductors colored black with
conductor number surface printed in contrasting ink
GROUND
• Uninsulated tinned annealed copper per ASTM B3
• Class B stranding per ASTM B8
JACKET
• Lead-free, fame-retardant thermoplastic Chlorinated Polyethylene (CPE)
STANDARDS
Industry Compliances:
• UL 44 Type XHHW-2
• UL 1277 Type TC-ER, UL File # E57179
• UL 1581
• ICEA S-95-658/NEMA WC70
Flame Test Compliances:
• UL 1581/UL 2556 VW-1
• UL 1685 Vertical Flame Test
• IEEE 383
• IEEE 1202
• CSA FT4
• ICEA T-29-520
Other Compliances:
• EPA 40 CFR, Part 261 for leachable
lead content per TCLP
• OSHA Acceptable NEED LUGS?
1 Approved as TYPE TC-ER for Exposed Run applications of
3 of more conductors as defned by NEC.
industrialsales@cobrawire.com | 216-416-0477 | www.cobrawire.com
© 2015 Cobra Wire & Cable, A Genuine Cable Group Company
A GENUINE CABLE GROUP COMPANY A DIVISION OF EIS, INC.
46