Page 64 - index
P. 64


EPR/PVC Copper Tape Shield 5kV


Medium-Voltage Power Cable • Shielded • 5kV

UL Type MV-105/ST1 • 133% Ins. Level • 220 Mils



CONDUCTOR
• 6 AWG thru 1000 kcmil annealed bare copper compact Class B strand


EXTRUDED STRAND SHIELD (ESS)
• Extruded thermoset semi-conducting stress-control layer over conductor insulation
• Ethylene Propylene Rubber (EPR) insulation, colored to
contrast with the black conducting shield layers

INSULATION

• Ethylene Propylene Rubber (EPR) insulation, colored to
contrast with the black conducting shield layers


EXTRUDED INSULATION SHIELD (EIS)
• Thermoset semi-conducting polymeric layer free stripping from insulation


METALLIC SHIELD
• 5 mil annealed copper tape with an overlap of 25%

OVERALL JACKET
• Lead-free, fame-retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)

STANDARDS
Industry Compliances:
• National Electrical Code (NEC)
• UL 1072
• ICEA S-93-639/NEMA WC74
• ICEA S-97-682
• AEIC CS8
• UL listed as Type MV-105 for use in accordance with NEC,
UL File # E90501
• UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test
• Sizes 1/0 AWG and larger are listed and marked “Sunlight-
Resistant FOR CT USE” in accordance with NEC
• IEEE 1202 (70,000 BTU/hr)/CSA FT4
• EPA 40 CFR, Part 261 for leachable lead content per TCLP method
• OSHA Acceptable
Optional Flame Tests:
• ICEA T-29-520 (210,000 BTU/hr)








industrialsales@cobrawire.com | 216-416-0477 | www.cobrawire.com
© 2015 Cobra Wire & Cable, A Genuine Cable Group Company
A GENUINE CABLE GROUP COMPANY A DIVISION OF EIS, INC.
64
   59   60   61   62   63   64   65   66   67   68   69