Page 64 - index
P. 64
EPR/PVC Copper Tape Shield 5kV
Medium-Voltage Power Cable • Shielded • 5kV
UL Type MV-105/ST1 • 133% Ins. Level • 220 Mils
CONDUCTOR
• 6 AWG thru 1000 kcmil annealed bare copper compact Class B strand
EXTRUDED STRAND SHIELD (ESS)
• Extruded thermoset semi-conducting stress-control layer over conductor insulation
• Ethylene Propylene Rubber (EPR) insulation, colored to
contrast with the black conducting shield layers
INSULATION
• Ethylene Propylene Rubber (EPR) insulation, colored to
contrast with the black conducting shield layers
EXTRUDED INSULATION SHIELD (EIS)
• Thermoset semi-conducting polymeric layer free stripping from insulation
METALLIC SHIELD
• 5 mil annealed copper tape with an overlap of 25%
OVERALL JACKET
• Lead-free, fame-retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)
STANDARDS
Industry Compliances:
• National Electrical Code (NEC)
• UL 1072
• ICEA S-93-639/NEMA WC74
• ICEA S-97-682
• AEIC CS8
• UL listed as Type MV-105 for use in accordance with NEC,
UL File # E90501
• UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test
• Sizes 1/0 AWG and larger are listed and marked “Sunlight-
Resistant FOR CT USE” in accordance with NEC
• IEEE 1202 (70,000 BTU/hr)/CSA FT4
• EPA 40 CFR, Part 261 for leachable lead content per TCLP method
• OSHA Acceptable
Optional Flame Tests:
• ICEA T-29-520 (210,000 BTU/hr)