EPR/PVC Copper Tape Shield 15kV



EPR/Copper Tape Shield/PVC • Medium-Voltage Power Cable

Shielded • 15kV • UL Type MV-105 • 133% Ins. Level • 220 Mils



CONDUCTOR

• 2 AWG thru 1000 kcmil annealed bare copper compact Class B strand

INSULATION
• Ethylene Propylene Rubber (EPR) insulation, colored to
contrast with the black conducting shield layers

SHIELDS
• Extruded Strand Shield (ESS) - Extruded thermoset semi-
conducting stress control layer over conductor
• Extruded Insulation Shield (EIS) - Thermoset semi-conducting
polymeric layer free stripping from insulation
• Metallic Shield - 5 mil annealed copper tape with an overlap of 25%


JACKET
• Lead-free, fame-retardant, moisture and sunlight-
resistant Polyvinyl Chloride (PVC)

STANDARDS
Industry Compliances:
• National Electrical Code (NEC)
• UL 1072
• AEIC CS8
• ICEA S-93-639/NEMA WC74
• ICEA S-97-682
• UL listed as Type MV-105 for use in accordance
with NEC, UL File # E90501
• UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test
• Sizes 1/0 AWG and larger are listed and marked “Sunlight
Resistant FOR CT USE” in accordance with NEC
• IEEE 1202 (70,000 BTU/hr)/CSA FT4
• EPA 40 CFR, Part 261 for leachable lead content per TCLP method
• OSHA Acceptable
Optional Flame Tests:
• ICEA T-29-520 (210,000 BTU/hr)