INSUL CONDUIT AMPACITY
COND. THICKNESS JACKET CABLE COPPER WT CABLE WT
PART NUMBER SIZE COND. THICKNESS O.D. SIZING CONDUIT UNDERGROUND TRAY LBS/1000 LBS/1000
O.D.
(4)
(AWG) MIN MAX INCHES INCHES INCHES IN AIR (1) DUCT (2) (3) FT FT
MVLS-002-15KV 2 0.27 0.710 0.800 0.080 0.99 3 165 165 - 276 658
MVLS-001-15KV 1 0.31 0.745 0.830 0.080 1.02 3.5 190 185 - 332 733
MVLS-110-15KV 1/0 0.34 0.780 0.865 0.080 1.06 3.5 215 215 220 403 825
MVLS-210-15KV 2/0 0.38 0.820 0.905 0.080 1.10 3.5 255 245 250 492 938

MVLS-310-15KV 3/0 0.43 0.865 0.955 0.080 1.14 3.5 290 275 290 603 1078
MVLS-410-15KV 4/0 0.48 0.920 1.005 0.080 1.21 3.5 330 315 335 743 1261
MVLS-250-15KV 250 0.53 0.970 1.060 0.080 1.25 4 365 345 370 866 1407
MVLS-350-15KV 350 0.62 1.070 1.155 0.080 1.35 5 440 415 460 1184 1783

MVLS-500-15KV 500 0.74 1.190 1.275 0.080 1.47 5 535 500 575 1657 2331
MVLS-750-15KV 750 0.91 1.370 1.460 0.080 1.65 6 655 610 745 2445 3234
MVLS-1000-15KV 1000 1.06 1.520 1.610 0.110 1.86 6 755 690 890 3228 4219

Dimensions and weights are nominal; subject to industry tolerances.
(1) Ampacities are in accordance with Table 310.60(C)(73) of the NEC for triplexed or three single conductor copper cable in isolated conduit in air, based on a conductor
temperature of 105ºC (221ºF) and an ambient air temperature of 40ºC (104ºF).
(2) Ampacities are in accordance with Table 310.60(C)(77) of the NEC for triplexed or three single conductor copper cable in underground ducts (three conductors per duct),
based on a conductor temperature of 105ºC (221ºF) and an ambient earth temperature of 20ºC (68ºF), electrical duct arrangement per Figure 310.60 Detail 1, 100% load
factor, and earth thermal resistance (rho) of 90.
(3) Ampacities are based on single conductor Type MV-105 sizes #1/0 AWG and larger in an uncovered tray in accordance with Section 392.80(B)(2) of the NEC at an
ambient air temperature of 40ºC (104ºF): the ampacities are based on 75% of the values per Table 310.60(C)(69). For cable trays with unventilated covers for more than 6
feet, the ampacities shall not exceed 70% of the values shown above.
(4) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fll. Jam ratio has been considered,
but it should be checked for individual installations.