TELCOFLEX® II
Central Office Power Wire and Cable
Class I Flexible Strand Without Braid
Low Smoke, Non-Halogenated Insulation, Lead-Free and Silicone-Free, UL Central Office Power Cable. 105°C Dry as AWM, 60°C Wet; UL Listed RHH/ST1 90°C Dry, 60°C Wet, 600 Volts. Sizes 1/0 AWG and larger are UL Listed for CT USE. CSA AWM I B 105°C 600 Volt FT4.
This specification covers the construction requirements for low smoke, non-halogenated central office power wire and cable, insulated with Southwire TelcoHyde®. UL listed Type RHH/ST1 for use in accordance with the National Electrical Code. The construction of the wire and cable is in accordance with Telcordia GR-347-CORE and KS-24194™ and ATIS-0600017.2014, Underwriters’ Laboratories requirements, and the requirements of CSA for the FT4 flame test. Sizes 1/0 AWG and larger are UL “CT Use” (Cable Tray) rated.
Size: Sizes 14 AWG through 750 KCMIL • Single conductor.
Conductors: Class I (modified) bunched (8 and 6 AWG) and rope-bunched (4 AWG and larger) stranded tinned copper conforming to ASTM B-33 and Underwriters’ Laboratories requirements. An opaque Mylar tape shall be applied over the conductor to facilitate stripping. Class K copper used with 14-10 AWG.
Insulation: 105°C rated low smoke, non-halogen TelcoHyde® conforming to Underwriters’ Laboratories Standard 44, Subjects 509 and 758, and CSA C22.2 No. 210-11. In addition, TelcoHyde® complies with the requirements of Telcordia Specification GR-347-CORE. The insulation has a Limiting Oxygen Index of 35%.
Separator: On sizes 6 AWG and larger, a 1 mil clear mylar tape shall be applied over the insulation.
Surface Marking: Two sides of the cable shall be printed using an ink of contrasting color and with the following information: “SOUTHWIRE AIW™ CORD BRAND TELCOFLEX® II/KS24194™ L2 NON-HAL (UL) E18321 SIZE (AWG or KCMIL) 600 VOLTS RHH ST1 FT4 OR AWM 3578 60°C WET VW-1 — LL8825 CSA AWM I B 105°C 600 VOLTS FT4-ST1 YEAR TIME JULIAN DATE — MEETS IEC INCLUDING 60674 & 60332”.
Note: KS24194™ L2 printed on 8-750 only. For sizes 1/0 AWG and larger add "FOR CT USE" before "(AWM 3578)" on Sizes 1/0 AWG and larger. Sequential footage markings shall be applied at 2 foot intervals on one side of the cable.
Testing: Physical and electrical tests in accordance with UL Standard 44 requirements, Subject 509 and 758; and CSA Standard C22.2 No. 210-11 as AWM.
Labels: UL tags and labels shall be applied to all packages.
Size | Stranding (24 AWG) | Nominal CMA | Conductor Diamter | Insulation Min Avg Walls | Nominal Insulation Diameter | MAX. DC RES @ 20°C | Ampacity per NEC Table 310.15 (B)(16) | |
---|---|---|---|---|---|---|---|---|
AWG | In | Mils | In | Ohms/MFT | 75°C | 90°C | ||
14 | 41 | 4110 | .077 | 45 | .170 | 2.730 | 20 | 25 |
12 | 65 | 6530 | .089 | 45 | .182 | 1.720 | 25 | 30 |
10 | 104 | 10380 | .116 | 45 | .209 | 1.080 | 35 | 40 |
8 | 41 | 16510 | .153 | 60 | .280 | .6790 | 50 | 55 |
6 | 65 | 26240 | .188 | 60 | .315 | .4360 | 65 | 75 |
4 | 105 | 41740 | ,260 | 60 | .385 | .2740 | 85 | 95 |
2 | 168 | 66360 | .305 | 80 | .430 | .1720 | 115 | 130 |
1 | 224 | 83690 | .370 | 80 | .540 | .1260 | 130 | 150 |
1/0 | 266 | 105600 | .392 | 80 | .560 | .1090 | 150 | 170 |
2/0 | 342 | 133100 | .455 | 80 | .620 | .0868 | 175 | 195 |
4/0 | 532 | 211600 | .577 | 80 | .745 | .0546 | 230 | 260 |
350 MCM | 888 | 350000 | .760 | 95 | .960 | .0334 | 310 | 350 |
500 MCM | 1221 | 500000 | .890 | 95 | 1.090 | .0234 | 380 | 430 |
750 MCM | 1850 | 750000 | 1.094 | 110 | 1.320 | .0157 | 475 | 535 |
TELCOFLEX® is a registered trademark of Southwire. TelcoHyde™ is a trademark of Southwire.